Product List
Hot Product
  • Low smoke low halogen flame retardant control cable
  • Shielded power cable
  • Welding Cable
  • 4/6 AWG Duplex Service Drop
  • Metal shielded power cable
  • TR-XLPE Insulated URD Cable
  • Low smoke low halogen flame r
  • Shielded power cable
  • Welding Cable
  • 4/6 AWG Duplex Service Drop
  • Metal shielded power cable
  • TR-XLPE Insulated URD Cable
Projects

600/1000V PVC Insulated Cable Without Sheath


600/1000V PVC Insulated Cable Without Sheath
Standard: BS 6500
Capacity: 2000KM/m
Voltage: 600/1000V
Application: used in power stations, public transport systems, airports, petrochemical factories, hotels, hospitals, high-rise buildings etc.
   


600/1000V PVC insulated power cable without sheath
BS 6500 PVC insulated flame retardant cable is mainly used in power stations, public transport systems, airports, petrochemical factories, hotels, hospitals, high-rise buildings etc.
 
Fire performance:
 
Flame retardant (single vertical cable test): EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NbN C 30-004 (cat. F1); NF C32-070-2.1 (C2); CEI 20-35/1-2; en 50265-2-1*; DIN VDE 0482-265-2-1*
 
Reduce the fire spread (vertically mounted into cable beam tests): en 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NbN C 30-004 (cat. F2); NF C32-070-2.2 (C1); CEI 20-22/3-4; en 50266-2-4*; DIN VDE 0482-266-2-4
 
Halogen: IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1;BS 6425-1*
 
Non corrosive gases: IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2; BS 6425-2*
 
The minimum smoke release: IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 
 
50268-1&2*; BS 7622-1&2*
 
No toxic gas: NES 02-713; NF C 20-454
 
Structure parameter:
 
Conductor FGD300 1V-R
Core number/Cross-sectional area Number of strands/Monofilament diameter Nominal insulation thickness Total nominal diameter About weight
NO×MM² NO./MM MM MM KG/KM
1×1.5 7/0.53 0.7 3.1 22
1×2.5 7/0.67 0.8 3.7 34
1×4 7/0.85 0.8 4.3 50
1×6 7/1.04 0.8 4.8 70
1×10 7/1.35 1.0 6.2 116
1×16 7/1.70 1.0 7.2 174
1×25 7/2.14 1.2 9.0 276
1×35 7/2.52 1.2 10.0 366
1×50 19/1.78 1.4 11.9 502
1×70 19/2.14 1.4 13.7 706
1×95 19/2.52 1.6 16.0 974
1×120 37/2.03 1.6 17.6 1213
1×150 37/2.25 1.8 19.6 1492
1×185 37/2.52 2.0 21.8 1868
1×240 61/2.25 2.2 24.4 2443
1×300 61/2.52 2.4 27.7 3055
1×400 61/2.85 2.6 31.1 3888
1×500 61/3.20 2.8 34.6 4880

Electrical performance:
 
The conductor operating temperature: 90°C
Around temperature: 30°C

Previous:Flame Retardant Cable       Next:Welding Cable